AFDD-32 type arc fault protection device is composed of miniature circuit breaker, tripping structure and arc detection module, and has short circuit protection, overload protection and arc fault protection functions, which are used in AC circuits with rated current of 32A and below.
The Acrel AFDD-32 arc fault protection device is composed of a miniature circuit breaker, a tripping mechanism, and an arc fault detection module. It provides short-circuit, overload, and arc fault protection for AC circuits with a rated current of 32 A or less, and it meets GB/T 31143-2014.
The manual covers the product overview, model, technical parameters, product characteristics, installation and wiring, indicator light definitions, key operation, product usage instructions, and precautions. The device is mounted on a 35 mm rail, and its indicators and test key are used to check operation and identify whether tripping was caused by an arc fault, short circuit, or overload. This manual is written in Chinese.
| Standard | GB/T 31143-2014 |
|---|---|
| Input rated voltage | AC 220 V |
| Rated current | AC 6 A, 10 A, 16 A, 20 A, 25 A, 32 A |
| Frequency | 50 Hz |
| Trip unit | B, C type |
| Rated insulation voltage (Ui) | 400 V |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Rated service short-circuit capacity (Ics) | 6 kA |
| Rated short-circuit capacity (Icn) | 6 kA |
| Insulation material group | IIIa |
| Grid distance | 40 mm |
| Ambient temperature | -5 to +55 °C |
| Relative humidity | Maximum 50% at 40 °C, maximum 90% at 20 °C |
| Altitude | ≤ 2000 m |
| Mounting | 35 mm rail mounting |
The rated current options are AC 6 A, 10 A, 16 A, 20 A, 25 A, and 32 A.
It is mounted on a 35 mm rail, and fixed terminals can be added for securing.
It simulates an arc fault so the device trips, the handle opens, and the lower-end power is disconnected, verifying normal operation.
The upstream power supply must be disconnected before connecting the incoming and outgoing terminals.