Acrel AFDD-32 Arc Fault Protection Device Installation and Operation Instructions

AFDD-32 type arc fault protection device is composed of miniature circuit breaker, tripping structure and arc detection module, and has short circuit protection, overload protection and arc fault protection functions, which are used in AC circuits with rated current of 32A and below.


Acrel AFDD-32 Arc Fault Protection Device Installation and Operation Instructions - cover page
Brand
Acrel
Category
Other
Document type
User Manual
Language
Chinese
Pages
7
File format
PDF
File size
285 KB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
36EECE630633BAE2511C4E2769CB08E8

About this manual

The Acrel AFDD-32 arc fault protection device is composed of a miniature circuit breaker, a tripping mechanism, and an arc fault detection module. It provides short-circuit, overload, and arc fault protection for AC circuits with a rated current of 32 A or less, and it meets GB/T 31143-2014.

The manual covers the product overview, model, technical parameters, product characteristics, installation and wiring, indicator light definitions, key operation, product usage instructions, and precautions. The device is mounted on a 35 mm rail, and its indicators and test key are used to check operation and identify whether tripping was caused by an arc fault, short circuit, or overload. This manual is written in Chinese.

What's inside

  • Overview
  • Product model
  • Technical parameters
  • Product characteristics
  • Installation and wiring
  • Mounting dimensions and method
  • Wiring instructions
  • Indicator definitions and key operation
  • Product usage instructions
  • Precautions

Specifications

StandardGB/T 31143-2014
Input rated voltageAC 220 V
Rated currentAC 6 A, 10 A, 16 A, 20 A, 25 A, 32 A
Frequency50 Hz
Trip unitB, C type
Rated insulation voltage (Ui)400 V
Rated impulse withstand voltage (Uimp)4 kV
Rated service short-circuit capacity (Ics)6 kA
Rated short-circuit capacity (Icn)6 kA
Insulation material groupIIIa
Grid distance40 mm
Ambient temperature-5 to +55 °C
Relative humidityMaximum 50% at 40 °C, maximum 90% at 20 °C
Altitude≤ 2000 m
Mounting35 mm rail mounting

Frequently asked questions

What is the rated current range of the Acrel AFDD-32?

The rated current options are AC 6 A, 10 A, 16 A, 20 A, 25 A, and 32 A.

How is the AFDD-32 mounted?

It is mounted on a 35 mm rail, and fixed terminals can be added for securing.

What is the test key used for?

It simulates an arc fault so the device trips, the handle opens, and the lower-end power is disconnected, verifying normal operation.

What should be done before installing the device?

The upstream power supply must be disconnected before connecting the incoming and outgoing terminals.

Download PDF (285 KB)