This manual introduces the basic principle, technical parameters, performance, circuit structure, human-machine interface, model description, cabinet appearance size, governance mode, installation instructions, and operating instructions of ANAPF active power filter.
The Acrel ANAPF series Active Power Filter is designed for low-voltage distribution systems to dynamically track and compensate for harmonic currents. It utilizes IGBT power modules and a PWM inverter to generate compensation currents that cancel out harmonics produced by nonlinear loads, while also offering reactive power compensation and three-phase current balancing. The device features a liquid crystal display (HMI) for monitoring status, controlling operations, and viewing historical data. This manual is written in Chinese.
| Input Voltage | 3×380V ±10% |
|---|---|
| Input Frequency | 50Hz ±2% |
| Response Time (Full) | ≤10ms |
| Response Time (Instant) | ≤100μs |
| Switching Frequency | 10-20kHz |
| Harmonic Compensation Range | 2-51 orders |
| Noise Level | < 65dB |
| Operating Temperature | -10℃~+45℃ |
| Cooling Method | Forced Air Cooling |
The device includes output limit protection, over-temperature protection, DC bus over-voltage protection, and input voltage under/over-voltage protection.
The unit is designed for indoor installation at an altitude of up to 1000m.
It detects harmonic currents via CTs, calculates the required compensation, and injects a current of equal amplitude but opposite phase to cancel the harmonics.