VICTOR 8100B transformer core grounding current tester is specially designed and manufactured for on-line testing of transformer core grounding current and leakage current in power systems. The instrument has anti-interference ability and can be used in strong magnetic field interference environment near transformer. It is mainly used for leakage current testing of iron cores and accessories of transformers, reactors, etc. in substations and power plants. It can also be used for current and leakage current testing of lines or equipment in fields such as power, communication, meteorology, railways, oil fields, construction, measurement, scientific research and teaching units, and mining enterprises.
This document provides detailed instructions for operating the VICTOR 8100B transformer core grounding current tester, including setup, measurement, data management, and safety precautions. The device is designed for testing transformer core grounding currents and leakage currents in power systems, with features like a 3.5-inch touchscreen, USB data export, and alarm settings. Safety warnings are prominently displayed throughout the manual to prevent electrical hazards during use.
The tester includes a clamp meter with an 80mm x 80mm jaw for non-contact measurements, and supports data storage for 200 groups. It operates on DC 9V alkaline batteries and is suitable for AC lines up to 600V. The manual covers all operational functions, including clock settings, data saving, and calibration procedures. This manual is written in Chinese.
| Current Range | AC 0.00mA~100A |
|---|---|
| Accuracy | ±(0.5%+5dgt) |
| Frequency Range | 10HZ~1000HZ |
| Display | 3.5 寸彩色触摸液晶屏(320dots×240dots) |
| Data Storage | 200 groups |
| Battery Type | DC 9V alkaline batteries (LR6 1.5V×6) |
| Clamp Jaw Size | 80mm × 80mm |
| Operating Temperature | -10℃~40℃ |
| Storage Temperature | -10℃~60℃ |
| Insulation Strength | AC 2kV/rms |
The tester cannot be used to test lines with voltage higher than 600V.
The device can store up to 200 groups of data.
Resolution varies by range: 0.01mA for 0.00mA–0.99mA, 0.1mA for 1.0mA–99.0mA, 1mA for 100mA–999mA, and 0.1A for 1.0A–100.0A.
The device defaults to automatic shutdown after 5 minutes of operation.