This user guide provides information on the configuration and use of the universal BACnet Router UBR-01 from MBS with Danfoss VLT® HVAC Drive FC 102 and VACON® 100 HVAC, using the embedded BACnet MS/TP communication.
This manual provides instructions for configuring the universal BACnet Router UBR-01 to enable communication between a BACnet network and Danfoss VLT HVAC Drive FC 102 or VACON 100 HVAC frequency converters. It covers network setup, cabling requirements for RS485 and Ethernet connections, and device addressing.
| Default IP Address | 192.168.0.1 |
|---|---|
| Default Subnet Mask | 255.255.255.000 |
| Default Baud Rate | 38400 Baud |
| Maximum Ethernet Cable Length | 100 m |
The default IP address is 192.168.0.1.
The baud rate should be set to 38400.
Open the Activate menu and click Activate to restart the router.