Introduces the features and characteristics of 2.3-7.2 kV medium voltage solid-state soft starters, including overview, specifications, design features, operation principle, protection, overload protection, control circuit, and electronic equipment
This manual provides detailed instructions for installing, operating, and programming AEG medium voltage solid state soft starters rated 2.3-7.2kV. It covers unit specifications, wiring, startup procedures, user interface, setpoint programming, metering, and maintenance. The system includes SCR-based motor control with programmable overload curves, phase imbalance protection, and communication options via RS-485/RS-422. It supports 50/60Hz power and includes thermal memory and event logging features.
The manual is structured into chapters covering introduction, connections, start-up, user interface, setpoint programming, metering, and troubleshooting. It includes wiring diagrams, setpoint configuration pages, and maintenance instructions for stack replacement and low-voltage testing.
| Unit Running Overload Capacity | 125% - Continuous, 500% - 60 seconds |
|---|---|
| Frequency | 50 or 60Hz, +2Hz hardware selectable |
| SCR Peak Inverse Voltage Ratings | 6500V - 19500V (model dependent) |
| Ambient Condition Design | 0° to 40°C (32° to 104°F), 5 - 95% relative humidity |
| Control Voltage | 120VAC (customer supplied) |
| Relays | 8 Relays (4 programmable): Form C contacts |
| BIL Rating | 2300V - 7200V |
| Overload Reset | Manual (default) or automatic |
| Thermal Memory | Retentive Thermal Memory |
| LCD Display | Alpha numeric LCD display |
| Keypad | 8 function keys with tactile feedback |
| Status Indicators | 12 LEDs include Power, Run, Alarm, Trip, Aux Relays |
| Remote Mount Capability | Up to 1000 circuit-feet from chassis |
| Operating Memory | SRAM loaded from EEPROM at initialization |
| Factory Default Storage | Flash EPROM, field replaceable |
| Customer Settings and Status | Non-volatile EEPROM, no battery backup necessary |
| Real Time Clock | Lithium ion battery for clock memory only |
| Protocol | Modbus RTU |
| Signal | RS-485, RS-422 or RS232 |
| Network Capacity | Up to 247 devices per mode |
| Motor Load Percent of FLA | Current Data A, B, C Phase Current, Avg Current, Ground Fault (Option) |
| Thermal Data | Remaining thermal register; thermal capacity to start |
| Start Data | Avg Start Time, Avg Start Current, Measured Capacity to start, time since last start |
| RTD Data (Option) | Temperature readings from up to 12 RTDs (6 stator RTDs) |
| Voltage Metering | kW, kVAR, PF, kWH |
120VAC (customer supplied) for 2 or 3 wire control.
Manual (default) or automatic reset.
Modbus RTU over RS-485, RS-422 or RS232.
Up to 247 devices per mode.
0° to 40°C (32° to 104°F).
2300V - 7200V.
5 amps, 240VAC max.
The overload circuit retains thermal condition of the motor regardless of control power status.
Up to 1000 circuit-feet from chassis using twisted, shielded wire and power source.