Rosemount 1199 Sealing Systems Quick Start Guide

Quick Start Guide, provides basic operating instructions for Rosemount 1199 Sealing Systems, including operating and maintenance considerations.


Rosemount 1199 Sealing Systems Quick Start Guide - cover page
Brand
Rosemount
Category
Industrial Robot
Document type
Quick Start Guide
Language
Spanish
Pages
12
File format
PDF
File size
404 KB
Published
18 October, 2023
Updated
18 October, 2023
MD5 checksum
49C08D52FC725AB81DDB26060FDCD92D

About this manual

This Quick Start Guide covers general handling and mechanical installation instructions for Rosemount 1199 sealing systems used with differential pressure level transmitters. It explains the function of remote seal systems, including the separation of the process fluid from the sensor using a thin flexible diaphragm and secondary fill fluid. The document also details the pressure transfer path from the process to the transmitter sensor. This manual is written in Spanish.

What's inside

  • Introducción
  • Prefacio
  • Generalidades sobre manipulación
  • Instalación mecánica
  • Rangos del transmisor
  • Tipos de sello 1199
  • Montaje del sistema de sello en aplicaciones de vacío
  • Aspectos a considerar sobre el aislamiento
  • Sellos bridados
  • Sellos roscados

Specifications

Maximum static pressure limit for vacuum applications25 mmHgA (0.5 psia)
Minimum bend radius for capillary tubing8 cm (3 in.)
Recommended mounting height for vacuum applications1 m (3 ft.) below the bottom tap
Maximum operating temperature for PVC coating100 °C (212 °F)
Torque specification for 2500 PSIG Carbon Steel bolts23 ft-lb
Torque specification for 5000 PSIG Carbon Steel bolts53 ft-lb
Torque specification for 5000 PSIG Stainless Steel bolts50 ft-lb
Torque specification for 10000 PSIG Carbon Steel bolts105 ft-lb

Frequently asked questions

What is the maximum static pressure limit for vacuum applications?

The maximum static pressure limit is 25 mmHgA (0.5 psia) to ensure the fill fluid remains in the liquid phase.

What is the minimum bend radius for the capillary tubing?

The minimum bend radius for the capillary tubing is 8 cm (3 in.).

Should the transmitter be mounted below the bottom tap in vacuum applications?

Yes, a general rule is to mount the transmitter approximately 1 m (3 ft.) below the bottom tap of the vessel.

Can the PVC coating on the capillary be exposed to temperatures near 100 °C?

No, the PVC coating will break at temperatures near 100 °C (212 °F).