This manual provides safety information for the Rosemount™ 3051S Series of Instrumentation, including installation, use, and maintenance requirements.
This document serves as a safety manual for the Rosemount 3051S Series of Instrumentation, including the Pressure, Flow, and Level Transmitters, Advanced Diagnostics, MultiVariable Transmitter, and Electronic Remote Sensor (ERS) System. It provides guidance on complying with safety instrumented systems (SIS) requirements.
The manual details installation and commissioning procedures, specifically addressing IEC 61508 relevant requirements and failure rates. It also outlines the process for conducting partial and comprehensive proof tests to ensure device reliability and safety.
| Certification Standard | IEC 61508 or Route 2H approach |
|---|---|
| SIL Capability (Route 1H) | SIL 2@HFT=0, SIL 3@HFT=1 |
| SIL Capability (Route 2H low demand) | SIL 2@HFT=0, SIL 3@HFT=1 |
| Failure Rate Unit | FIT (Failures In Time per billion hours) |
Failure rates vary by model and option; for example, the Coplanar DP and Gage model has a Lambda SU of 82 and Lambda DD of 274.
Version information can be viewed on the handheld communicator or AMS at Home → Overview → Device information → Revisions.
FIT stands for Failures In Time per billion hours.