This manual introduces the installation and use of the Schneider Electric ALTISTART® 48 Y series soft starters, including installation, wiring, application, protection, and programming.
This document provides the installation guide for the ALTISTART® 48 (ATS48) soft starter controllers manufactured by Schneider Electric. It covers the quick start procedure, receiving and handling precautions, technical data, mounting requirements, and wiring instructions for standard and severe duty applications.
The guide details the factory configuration settings, programming menus, fault management procedures, and recommended wiring diagrams. It specifies that the controller uses patented torque-based control technology for smooth motor acceleration and deceleration, available in current ratings from 17 to 1200 A for voltages between 208 and 690 V.
| Current Ratings | 17 to 1200 A |
|---|---|
| Rated Voltage | 208 to 690 V |
| Supply Frequency | 50 or 60 Hz |
| Motor Type | Three-phase asynchronous induction |
| Control Supply | 115 V or 230 Vac |
The factory preset value for the Current Limit is 400% of the motor current IN.
The factory preset value for the Acceleration ramp is 15 seconds.
The initial torque on starting is preset to 20% of the nominal torque.
The default transmission speed is 19200 bits per second.