Installation and maintenance instructions for the Type N550 Emergency Shutoff Valves and Accessories
The Fisher Type N550 Snappy Joe emergency shutoff valves are lever-operated, latch-open, and quick-closing valves designed for in-line use on LP-Gas or Anhydrous Ammonia (NH3) service. They are intended for installation on transfer hoses connecting bulk plant piping to bobtail trucks, transport vehicles, or tank cars. The valves provide a quick way to shut off gas flow in the event of a hose rupture and meet requirements when correctly installed with a remote release and proper piping support. A fusible element in the latch melts at 212°F (100°C) to allow the valve to close automatically.
| Service | Butane, Propane, or NH3 |
|---|---|
| Temperature Range | -40° to 212°F (-40° to 100°C) |
| Maximum Inlet Pressure | 400 psig (27,6 bar) |
| Remote Air Supply Pressure | 30 to 70 PSIG (2,1 to 4,8 bar) |
A fusible element in the latch melts if the temperature reaches 212°F (100°C), allowing the valve to close.
A fusible element that will close the Type N550 shall be located within five feet of the hose connection.
The valve shall be installed to shutoff flow from the tank towards the hose, enabling the valve to control product loss in case of a hose break.