This document provides a set of guidelines for developers creating application programs using the Carel 1Tool software. It covers essential practices for maintaining code quality, including project archiving, standardizing programming styles, and ensuring code readability for other developers.

The manual details specific rules for the layout of objects on the page, variable naming conventions, and the use of references. It also includes instructions for managing the user interface, such as screen indexing and parameter consistency, to ensure a uniform and professional application structure.

What's inside

  • Programming style
  • Layout of objects
  • Variable names
  • References
  • Programming style in User interface
  • Miscellaneous
  • Migrated project
  • User interface rules

Frequently asked questions

What value should be assigned to the Copy_Password system variable if no specific value is designated in the development specifications?

The value 0 (zero) must be assigned to the Copy_Password system variable.

Why must absolute timers of any kind be avoided when controlling the sequence of operations?

Using absolute timers causes incompatibility errors due to differences in the execution speed of controllers when changing hardware.

What is the minimum step size required for references used in a routine?

References must not be consecutive and must use a step of at least 10.