Carel MC Room Humidification System Installation Operation & Maintenance Manual

This manual provides instructions for installing, operating, and maintaining CAREL MC room humidifiers.


Carel MC Room Humidification System Installation Operation & Maintenance Manual - cover page
Brand
Carel
Document type
User Manual
Language
English
Pages
28
File format
PDF
File size
545 KB
Published
13 October, 2023
Updated
13 October, 2023
MD5 checksum
BE8E895CD74C30C4BE2D031D51D5A0B4

About this manual

The document provides comprehensive instructions for installing the Carel MC atomizing humidification system. It details assembly rules, layout planning, cabinet mounting, and connections for air, water, and electrical power. The guide also includes specific wiring diagrams and sensor installation procedures to ensure safe and efficient operation.

Operation and maintenance sections explain how to use the control keyboard, access parameters, change setpoints, and perform routine maintenance. The manual concludes with troubleshooting instructions, a list of parts for atomizing heads and control cabinets, and technical specifications.

What's inside

  • Installation Rules
  • Assemble Atomizing Head Assemblies
  • Plan System Layout
  • Mount the Cabinet
  • Connect Air and Water
  • Connect Electric Power
  • Operating the MC Controls
  • Maintenance Instructions
  • Trouble Shooting Instructions
  • Technical Specifications

Specifications

Compressed air pressure requirement at cabinet100 psi
Discharge pressure to atomizing heads30 psi at manifold ends
Water pressure requirement at atomizing manifolds5 psi
Minimum recommended water pressure to cabinet20 psi
Maximum water pressure to cabinet100 psi maximum
Minimum air line size for systems over 200 lbs/hr or over 100 feet3/4" I.D.

Frequently asked questions

What are the compressed air requirements for the MC system?

The system requires clean compressed air without oil, fed at 100 psi to the cabinet and reduced to 30 psi at the atomizing heads. Minimum equipment includes an after cooler, moisture separator, trap, and a 0.1 micron coalescing filter.

What water pressure is required for the atomizing manifolds?

The system requires 5 psi of clean water at the atomizing manifolds.

What is the warranty period for Carel MC products?

All products are warranted to be free from defects in materials and workmanship for a period of 2 years from the date of installation or 2 years and 1 month from the date of shipment, whichever comes first.