Unitronics Vision PLC+HMI Installation Guide V130/V350/V430

This manual introduces the features and characteristics of Unitronics V130-TR6/V130-J-TR6/V350-35-TR6/V350-J-TR6/V430-J-RH6 micro-PLC+HMIs.


Unitronics Vision PLC+HMI Installation Guide V130/V350/V430 - cover page
Brand
Unitronics
Category
Industrial Robot
Document type
Installation Guide
Language
English
Pages
12
File format
PDF
File size
772 KB
Published
12 October, 2023
Updated
12 October, 2023
MD5 checksum
27B4766647089B559542BABDE0B61BED

About this manual

This guide provides installation instructions for Unitronics Vision™ PLC+HMI controllers, specifically models V130, V350, and V430. It details the mounting procedures for both panel and DIN-rail applications, including specific cut-out dimensions and torque requirements for securing the device.

What's inside

  • General Description
  • Alert Symbols
  • Environmental Considerations
  • Panel Mounting
  • DIN-rail Mounting
  • Wiring Procedure
  • Input Jumper Settings
  • I/O Wiring
  • Power Supply
  • Communication

Specifications

Digital Inputs8 Digital Inputs, including 2 Analog, 1 HSC/Shaft-encoder inputs
Analog Inputs4 Analog Inputs (Current)
Relay Outputs6 Relay Outputs
High-speed Outputs2 high-speed npn Transistor Outputs (TR6 Only)
Panel Cut-out (V130/V350)92x92 mm (3.622"x3.622")
Panel Cut-out (V430J)122.5x91.5 mm (4.82"x3.6")
Mounting Torque0.4 N·m (4 kgf·cm)
Wire Torque Limit0.5 N·m (5 kgf·cm)
Wire Gauge3.31 mm² –0.13 mm² (12-16 AWG)
Power SupplyExternal 24VDC

Frequently asked questions

What are the panel mounting dimensions for V130 and V350 models?

The panel cut-out size for V130/V350/V130J/V350J models is 92x92 mm (3.622"x3.622").

What is the required torque for tightening mounting bracket screws?

The necessary torque for mounting is 0.4 N·m (4 kgf·cm).

What wire gauge is recommended for wiring the controller?

Use crimp terminals with 3.31 mm² –0.13 mm² wire (12-16 AWG).

Can the V430J model be used with a PC via USB?

Yes, V430J models comprise a built-in USB port, but connecting a PC via USB suspends RS232/RS485 communications.