This manual introduces the features and characteristics of Unitronics V130-TR6/V130-J-TR6/V350-35-TR6/V350-J-TR6/V430-J-RH6 micro-PLC+HMIs.
This guide provides installation instructions for Unitronics Vision™ PLC+HMI controllers, specifically models V130, V350, and V430. It details the mounting procedures for both panel and DIN-rail applications, including specific cut-out dimensions and torque requirements for securing the device.
| Digital Inputs | 8 Digital Inputs, including 2 Analog, 1 HSC/Shaft-encoder inputs |
|---|---|
| Analog Inputs | 4 Analog Inputs (Current) |
| Relay Outputs | 6 Relay Outputs |
| High-speed Outputs | 2 high-speed npn Transistor Outputs (TR6 Only) |
| Panel Cut-out (V130/V350) | 92x92 mm (3.622"x3.622") |
| Panel Cut-out (V430J) | 122.5x91.5 mm (4.82"x3.6") |
| Mounting Torque | 0.4 N·m (4 kgf·cm) |
| Wire Torque Limit | 0.5 N·m (5 kgf·cm) |
| Wire Gauge | 3.31 mm² –0.13 mm² (12-16 AWG) |
| Power Supply | External 24VDC |
The panel cut-out size for V130/V350/V130J/V350J models is 92x92 mm (3.622"x3.622").
The necessary torque for mounting is 0.4 N·m (4 kgf·cm).
Use crimp terminals with 3.31 mm² –0.13 mm² wire (12-16 AWG).
Yes, V430J models comprise a built-in USB port, but connecting a PC via USB suspends RS232/RS485 communications.