Unitronics Vision PLC+HMI Installation Guide V130/V350/V430 Series

Unitronics 1 Vision™PLC+HMI Installation Guide, introduces the features of V130-33-TR34/V130-J-TR34, V350-35-TR34/V350-J-TR34, V430-J-TR34 products, including 22 digital inputs, 3 HSC/Shaft-encoder inputs, 2 analog inputs, 8 relay outputs, 4 high-speed npn transistor outputs, 2.4-inch, 3.5-inch color touch screen, keyboard, function keys, RS232/485, USB interface


Unitronics Vision PLC+HMI Installation Guide V130/V350/V430 Series - cover page
Brand
Unitronics
Document type
Installation Guide
Language
English
Pages
12
File format
PDF
File size
928 KB
Published
12 October, 2023
Updated
12 October, 2023
Models
V130, V350, V430
MD5 checksum
44C096B5805C0D62EEBE4B5A554D58BA

About this manual

The document provides an installation guide for the Unitronics Vision™ PLC+HMI series, covering models V130, V350, and V430. It details hardware specifications such as digital inputs, analog inputs, relay outputs, and transistor outputs available across different variants (TR34/R34).

The guide includes instructions for panel mounting and DIN-rail mounting, along with specific wiring procedures for inputs and outputs. It also covers power supply requirements, earthing practices to minimize electromagnetic interference, and communication setup via RS232/RS485 ports or USB.

What's inside

  • General Description
  • Alert Symbols and Restrictions
  • Panel Mounting
  • DIN-rail Mounting
  • Wiring Procedures
  • I/Os Configuration
  • Analog Input Wiring
  • Power Supply Requirements
  • Communication Setup

Specifications

On-board I/O TypeMicro-PLC+HMI with built-in operating panels and on-board I/ Os
Digital Inputs (TR34 models)22 Digital Inputs, including 3 HSC/Shaft -encoder Inputs
Panel Cut-out Size (V130/V350)92x92 mm
Panel Cut-out Size (V430J)122.5x91.5 mm
Power Supply RequirementExternal 24VDC power supply

Frequently asked questions

What is the maximum torque for tightening terminal screws?

Do not exceed a maximum torque of 0.5 N·m (5 kgf·cm).

Can inputs be configured as analog?

Yes, Inputs 14 and 15 can function as either digital or analog inputs depending on jumper settings.

What is the maximum number of devices in an RS485 network?

Up to 32 devices.