This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation of the FX2N-4AD-TC special function block and should be read and understood before attempting to install or use the unit.
The FX2n-4AD-TC is a programmable controller analog input block designed to amplify signals from four thermocouple sensors (Type K or J) and convert them into 16-bit readings. It supports both Centigrade and Fahrenheit measurements and connects to various Mitsubishi Electric PLC series via the expansion bus.
The manual provides instructions on wiring, including the use of compensating cables for Type K and J thermocouples, grounding procedures, and terminal screw torque specifications. It also explains how to configure buffer memories (BFM) to select thermocouple types, set averaging parameters, and monitor error statuses.
| Input Signal Type | Thermocouple: Type K or J (4 channels) |
|---|---|
| Type K Temperature Range | -100°C to +1,200°C (-148°F to +2,192°F) |
| Resolution (Type K) | 0.4°C / 0.72°F |
| Resolution (Type J) | 0.3°C / 0.54°F |
| Overall Accuracy | + (0.5% full scale +1°C) |
| Conversion Speed | (240ms + 2%) x 4 channels |
| Power Supply (Analog) | 24V DC ±10%, 50mA |
| Weight | Approx. 0.3 kg (0.66 lbs) |
The unit supports Type K and Type J thermocouples for each channel.
The A/D conversion time is 240ms per channel.
The FX2n-4AD-TC occupies 8 I/O points on the PLC expansion bus.
The identification code read from buffer memory BFM #30 is K2030.