This file introduces the connection method between GP and Hitachi Ltd. PLCs, system structure, and the type of connection cables
This manual covers the system structure for connecting Pro-face GP-PRO/PBIII devices to various Hitachi Ltd. PLC series, including the S10a, S10 mini, EC, and S10V series. It details the specific cable diagrams required for RS-232C and RS-422 connections using Digital's adapters or custom-made cables.
The document also lists the supported device addresses (Input Relay, Output Relay, Internal Relay, etc.) for the GP-PRO/PBIII and provides recommended communication setup parameters, such as baud rate, data length, stop bit, parity, and data flow control, for each supported PLC model.
| Baud Rate (Hitachi S10a/S10 mini) | 19200 bps |
|---|---|
| Baud Rate (Hitachi EC Series) | 9600 bps |
| Data Length (Hitachi S10a/S10 mini) | 8 bits (fixed) |
| Data Length (Hitachi EC Series) | 7 bits |
| Parity Bit (Hitachi S10a/S10 mini) | Odd (fixed) |
| Parity Bit (Hitachi EC Series) | Even |
| Max Cable Length (RS-232C) | less than 15m |
| Max Cable Length (RS-422) | 500m or less |
For RS-232C connections, use a cable length less than 15m.
The manual specifies a maximum cable length of 500m or less for RS-422 connections.