This manual describes how to connect GP to Fuji Electric PLCs, including connection methods, cable diagrams, and system structures.
The document serves as a guide for establishing communication between the GP-PRO/PBIII programming tool and Fuji Electric Corporation PLCs. It details system structures and specific connection requirements for different product lines such as the MICREX-F Series (using Link I/F or CPU Direct Connection), MICREX-SX Series, FLEX-PC Series, and others.
The manual covers hardware interfacing by providing cable diagrams and specifications for RS-232C and RS-422 connections. It includes information on using specific cables like the Digital GP410-IS00-O or creating custom cables, along with important notes on grounding and termination resistors.
| Baud Rate (MICREX-SX CPU Direct) | 38400 bps |
|---|---|
| Data Length (MICREX-SX CPU Direct) | 8 bits |
| Stop Bit (MICREX-SX CPU Direct) | 1 bit |
| Parity Bit (MICREX-SX CPU Direct) | Even |
For the RS-232C connection, use a cable length less than 15m.
Simultaneous connection is only possible when the link units are attached directly to the main PLC unit.
A termination resistance of 100Ω must be added between RDA and RDB.