Woodward 82389 Electronic Load Sharing and Speed Control Installation and Operation Manual

This product manual provides installation and operation instructions for the 82389 Electronic Load Sharing and Speed Control equipment, including general precautions and proper use guidelines.


Woodward 82389 Electronic Load Sharing and Speed Control Installation and Operation Manual - cover page
Brand
Woodward
Category
Industrial Robot
Document type
User Manual
Language
English
Pages
51
File format
PDF
File size
989 KB
Published
09 March, 2023
Updated
28 September, 2023
MD5 checksum
E4EE87F3C040F6B321270C7E5C0AC254

About this manual

The Woodward 2301A Electronic Load Sharing and Speed Control (LSSC) is designed for use with generators driven by diesel or gasoline engines, as well as steam or gas turbines. This manual covers the complete lifecycle of the device, including unpacking, installation requirements, and electrical connections. It details the setup of speed ranges, potential and current transformer connections, and the configuration of droop contacts and load sharing lines.

What's inside

  • General Information
  • Installation
  • Operation and Adjustment
  • Description of Operation
  • Troubleshooting
  • Product Support and Service Options
  • Control Specifications
  • Warnings and Notices
  • Regulatory Compliance
  • Electrostatic Discharge Awareness

Specifications

Power Supply Rating90–150 Vdc or 85–132 Vac for High Voltage models
Power Supply Rating20–40 Vdc for Low Voltage models
Power Consumptionless than or equal to 15 W nominal
Operating Temperature-40 to +85 °C (–40 to +185 °F)
Weightapproximately 1.8 kg (4 lb)
Speed Control Range500–1500 Hz, 1000–3000 Hz, 2000–6000 Hz (standard), 4000–12 000 Hz

Frequently asked questions

What safety equipment should be worn when working with this control?

Always wear appropriate personal protective equipment (PPE) including eye protection, hearing protection, hard hat, gloves, safety boots, and a respirator.

What is the maximum actuator output current?

The actuator provides a maximum of 214 mA with a 35 Ω coil.

What is the maximum load gain at 5 A CT current?

The maximum load gain is 6 Vdc at 5 A CT current.

Download PDF (989 KB)