MH-Z19B carbon dioxide (CO2) gas sensor is a universal intelligent small sensor that uses non-dispersive infrared (NDIR) principle to detect CO2 in the air. It has good selectivity, no oxygen dependence, long lifespan, etc. It has built-in temperature compensation and provides UART and PWM output for easy use.
The document is a user manual for the Winsen MH-Z19B infrared (NDIR) carbon dioxide gas sensor. It describes the product's features, such as high sensitivity, low power consumption, and built-in temperature compensation, along with its applications in HVAC, air quality monitoring, and smart home systems.
The guide details technical specifications including operating voltage, measurement ranges, response time, and environmental limits. It also provides pin definitions for both header and terminal versions, explains how to calculate CO2 concentration from PWM output signals, and lists important precautions regarding installation, calibration, and soldering. This manual is written in Chinese.
| Operating Voltage | 4.5~5.5VDC |
|---|---|
| Average Current | <20mA (at 5V) |
| Measurement Range | 400~10000ppm |
| Output Signal | UART (TTL 3.3V), PWM |
| Preheat Time | 3min |
| Response Time (T90) | <120s |
| Operating Temperature | -10℃~50℃ |
The sensor offers selectable ranges including 400~2000ppm, 400~5000ppm, and 400~10000ppm.
The formula depends on the selected range; for example, for 400-2000ppm, Cppm=2×(TH-2ms), where TH is the high-level time.
Use a temperature setting of (350±5)℃ and keep the welding time under 3 seconds.
The manual suggests a calibration cycle of no more than 6 months.