This application note explains the procedure for designing the RS-485 communication lines in energy metering applications which helps e-meter engineers build their projects.
This document provides guidance for engineers designing RS-485 communication lines specifically for energy metering applications. It covers the selection of network architectures, such as bus or daisy chain, and highlights the benefits of using twisted pair cables with RS-485 differential transmission for robustness in noisy environments.
The note details critical design considerations including signal levels, bus length limitations up to 1 km, and the need for network isolation to prevent ground loops and damage from common-mode voltages. It also covers fail-safe biasing techniques to ensure valid logic states when receivers are disconnected or the bus is idle.
| Maximum signaling rate | 250 kbit/s |
|---|---|
| Maximum cable length | 1 km |
| Driver differential output voltage | at least 1.5 V |
| Receiver differential detection voltage | 200 mV |
| Maximum unit loads | 32 |
| Optocoupler rise/fall time requirement | 1.2 msec |
| Fail-safe biasing resistor value | 500/600 Q |
Most e-meter applications require signaling rates below 250 kbit/s.
The ST485EB supports cable lengths up to 1 km at signaling rates below 250 kbit/s.
RS-485 drivers must produce a differential output voltage of at least 1.5 V into a 54 Q load.
An optocoupler with rise/fall times faster than 1.2 msec is required for a signaling rate of 250 kbit/s.