ABB NLON-01 LonWorks Adapter FAQ

The NLON-01 adapter has downloadable applications for different drive types, with the default application in the adapter being for ACS600. If the application is not correct for the drive and the NLON-01 has been configured with a network management tool, the POW/ERR LED on the adapter will blink between red and green at a rate of 1 Hz. The appropriate application file to be loaded depends on the tool used. Most network management tools can download the application, but current versions of The Trane Company's Rover tool and Tridium's tool cannot. Like all DDCS fieldbus adapters, parameter 5005 must be set to DDCS (or Modus + DDCS) to enable communication between the adapter and the drive. When DDCS communication between the NLON-01 and ACH400 is working, parameter 51.01 should show 7. Parameters in group 51 are read-only values and manually changing them has no effect on the NLON-01.


ABB NLON-01 LonWorks Adapter FAQ - cover page
Brand
ABB
Category
Automation control Equipment
Document type
Other
Language
English
Pages
2
File format
PDF
File size
32 KB
Published
22 March, 2012
Updated
28 September, 2023
Model
NLON-01
MD5 checksum
38E3EB2CB73FA6B21728543911102756

About this manual

This FAQ document from ABB Inc. provides answers to common questions about the NLON-01 LonWorks adapter. It covers topics such as connecting the adapter to ACH400 drives, selecting the correct application and XIF files, and configuring start commands and references.

The document also addresses intermittent communication issues related to the FTT-10A transceiver and electromagnetic fields, as well as drive behavior after installing a LonWorks network with LonMaker.

What's inside

  • My adapter does not connect to ACH400
  • Which *.XIF should I use?
  • Where is the start command from LonWorks given?
  • I’m able to start the drive, but can’t give the reference.
  • I have intermittent communication problems with the NLON-01 adapter.
  • Drive is behaving strangely after installing the LonWorks network.

Specifications

TransceiverFTT-10A

Frequently asked questions

Why does the NLON-01 adapter not connect to an ACH400 drive?

The default application in the NLON-01 is for ACS600, so the correct application for the drive type must be downloaded. Parameter 5005 must also be set to DDCS or Modbus + DDCS for communication between the adapter and the drive.

Which XIF file should be used with the NLON-01?

Files with 'a' at the end are for Windows API based tools, and files without 'a' are for LNS based tools. Tridium's tool does not use the standard XIF file and requires a Shadow Object from Tridium.

How is the drive started from LonWorks with the NLON-01?

The start command is part of the SNVT_switch network variable used to give speed or setpoint. The nciExt1Ext2Sel state part selects whether nviDrvSpeedStpt or nviRefStpt starts the drive.

What can cause intermittent communication problems with the NLON-01 adapter?

The NLON-01 uses an FTT-10A transceiver that is sensitive to electromagnetic fields. The adapter should be placed as far as possible from power cables, and grounded sheet metal or turning the adapter 90 degrees may help.