The NLON-01 adapter has downloadable applications for different drive types, with the default application in the adapter being for ACS600. If the application is not correct for the drive and the NLON-01 has been configured with a network management tool, the POW/ERR LED on the adapter will blink between red and green at a rate of 1 Hz. The appropriate application file to be loaded depends on the tool used. Most network management tools can download the application, but current versions of The Trane Company's Rover tool and Tridium's tool cannot. Like all DDCS fieldbus adapters, parameter 5005 must be set to DDCS (or Modus + DDCS) to enable communication between the adapter and the drive. When DDCS communication between the NLON-01 and ACH400 is working, parameter 51.01 should show 7. Parameters in group 51 are read-only values and manually changing them has no effect on the NLON-01.
This FAQ document from ABB Inc. provides answers to common questions about the NLON-01 LonWorks adapter. It covers topics such as connecting the adapter to ACH400 drives, selecting the correct application and XIF files, and configuring start commands and references.
The document also addresses intermittent communication issues related to the FTT-10A transceiver and electromagnetic fields, as well as drive behavior after installing a LonWorks network with LonMaker.
| Transceiver | FTT-10A |
|---|
The default application in the NLON-01 is for ACS600, so the correct application for the drive type must be downloaded. Parameter 5005 must also be set to DDCS or Modbus + DDCS for communication between the adapter and the drive.
Files with 'a' at the end are for Windows API based tools, and files without 'a' are for LNS based tools. Tridium's tool does not use the standard XIF file and requires a Shadow Object from Tridium.
The start command is part of the SNVT_switch network variable used to give speed or setpoint. The nciExt1Ext2Sel state part selects whether nviDrvSpeedStpt or nviRefStpt starts the drive.
The NLON-01 uses an FTT-10A transceiver that is sensitive to electromagnetic fields. The adapter should be placed as far as possible from power cables, and grounded sheet metal or turning the adapter 90 degrees may help.