Communication protocol for ColliHigh network temperature and humidity transmitters by Kunlun Industrial Control, compliant with the MODBUS standard. Supports master-slave mode for querying temperature and humidity data. Data upload requires conversion and division by ten. Communication settings include 8 data bits, no parity, 1 stop bit, and selectable baud rates of 1200, 2400, 4800, and 9600.
The document describes the communication protocol for the Kunlun ColliHigh network temperature and humidity transmitter. It uses MODBUS-standard hexadecimal frames in a master-slave query mode, with configurable baud rates of 1200, 2400, 4800, or 9600 bit/s and a 7-bit DIP-switch address setting. A C-language CRC algorithm is provided for checksum verification. This manual is written in Chinese.
| Communication standard | MODBUS standard (hexadecimal) |
|---|---|
| Baud rates | 1200, 2400, 4800, 9600 bit/s |
| Default baud rate | 9600 bit/s |
| Serial format | 8 data bits, no parity, 1 stop bit |
| Default address | 01 |
It supports 1200, 2400, 4800, and 9600 bit/s, with 9600 bit/s set at the factory.
The address is set with a 7-bit DIP switch; for example, 0000001 corresponds to address 01.
Subtract the hex value from 0xFFFF; for example, FF8C yields 115, meaning -11.5°C.
The default address is 01.