Kunlun ColliHigh Network Temperature and Humidity Transmitter Communication Protocol

Communication protocol for ColliHigh network temperature and humidity transmitters by Kunlun Industrial Control, compliant with the MODBUS standard. Supports master-slave mode for querying temperature and humidity data. Data upload requires conversion and division by ten. Communication settings include 8 data bits, no parity, 1 stop bit, and selectable baud rates of 1200, 2400, 4800, and 9600.


Kunlun ColliHigh Network Temperature and Humidity Transmitter Communication Protocol - cover page
Brand
Collihigh
Category
Temperature sensors
Document type
Product Leaflet
Language
Chinese
Pages
3
File format
PDF
File size
114 KB
Published
19 March, 2012
Updated
28 September, 2023
MD5 checksum
37B01D82B98AF49DC1152612A91EC9F2

About this manual

The document describes the communication protocol for the Kunlun ColliHigh network temperature and humidity transmitter. It uses MODBUS-standard hexadecimal frames in a master-slave query mode, with configurable baud rates of 1200, 2400, 4800, or 9600 bit/s and a 7-bit DIP-switch address setting. A C-language CRC algorithm is provided for checksum verification. This manual is written in Chinese.

What's inside

  • MODBUS standard hex communication
  • Master-slave query for temperature and humidity data
  • Data format and temperature/humidity conversion
  • Serial format and baud rate settings
  • Baud rate and address DIP switch settings
  • CRC check algorithm in C

Specifications

Communication standardMODBUS standard (hexadecimal)
Baud rates1200, 2400, 4800, 9600 bit/s
Default baud rate9600 bit/s
Serial format8 data bits, no parity, 1 stop bit
Default address01

Frequently asked questions

What baud rates does the transmitter support?

It supports 1200, 2400, 4800, and 9600 bit/s, with 9600 bit/s set at the factory.

How is the device address configured?

The address is set with a 7-bit DIP switch; for example, 0000001 corresponds to address 01.

How are negative temperatures converted from the received data?

Subtract the hex value from 0xFFFF; for example, FF8C yields 115, meaning -11.5°C.

What is the factory default communication address?

The default address is 01.