LEM AHR-B5 AC/DC Current Transducer Datasheet

This PDF document is the detailed parameter manual of LEM's 500-2000A current transformer, which introduces the product's features and characteristics, including current measurement, T-RMS output, bus bar or panel mounting, insertion loss, application range, etc.


LEM AHR-B5 AC/DC Current Transducer Datasheet - cover page
Brand
LEM
Category
Current Monitor
Document type
Datasheet
Language
English
Pages
4
File format
PDF
File size
688 KB
Published
17 January, 2012
Updated
30 September, 2023
MD5 checksum
FD4C3410D31AA513F553B09E4AB88FD3

About this manual

The LEM AHR-B5 is an AC/DC current transducer for electronic measurement of DC and distorted AC waveform currents, with galvanic isolation between the primary and secondary circuits. It provides True RMS measurement with a 0-5 V DC voltage output.

The datasheet lists electrical, performance, general, isolation, transfer, mechanical and connection data, along with safety and warning notes, dimensions and remarks.

What's inside

  • Electrical data
  • Performance data
  • General data
  • Isolation characteristics
  • Transfer characteristics
  • Safety and warning notes
  • Mechanical characteristics
  • Dimensions
  • Connections
  • Remarks

Specifications

Primary nominal current (IPN)500, 800, 1000, 1500, 2000 A (rms)
Output voltage (VOUT)0-5 V DC
Load resistance (RL)≥ 10 kΩ
Supply voltage (VC)+20 to +50 V DC
Current consumption (IC)35 mA
Output voltage limitation (VSL)< 7 V
Overload capability (ÎP)30000 At
Accuracy (X)< ±1 % of IPN
Linearity error (εL)< ±1.0 % of IPN
Electrical offset voltage (VOE)< ±1.0 % of IPN
Temperature coefficient of VOE (TCVOE)±2.0 mV/K (0 to +60 °C); ±4.0 mV/K (-40 to +70 °C)
Temperature coefficient of VOUT (TCVOUT)±0.15 %/K
Response time (tr)< 150 ms
Frequency bandwidth (BW)DC, 20 to 6000 Hz (±1 dB)
Ambient operating temperature (TA)-40 to +70 °C
Ambient storage temperature (TS)-40 to +85 °C
Mass (m)650 g
Protection degree (IPxx)IP20
Primary aperture104 x 40 mm
General tolerance±1 mm
Busbar fastening1 hole ∅5.5 mm and 2 slots 5.5 x 30 mm
Panel mounting4 holes ∅3.2 mm; distance between hole axes 15 x 150 mm
Wiresup to 2 mm diameter
ConnectorFemale connector provided (screw terminals)

Frequently asked questions

What supply voltage does the AHR-B5 require?

The transducer requires a supply voltage of +20 to +50 V DC.

What is the output voltage range?

The analog output voltage is 0-5 V DC.

What is the ambient operating temperature range?

The ambient operating temperature range is -40 to +70 °C.

What is the primary aperture size?

The primary aperture is 104 x 40 mm.

Download PDF (688 KB)

More LEM Manuals


View all LEM manuals →