Fault code9
Undervoltage (fault) occurs when DC link voltage drops below limits, supply voltage is too low, or a component is defective. The manual's first action is: “If there is a temporary supply voltage break, reset the fault and restart the drive.”
- Model
- Vacon 100 Flow
- Display shows
- Undervoltage (fault) (9)
- Type
- Fault code
- Source
- Manual p. 369
What 9 means
Undervoltage (fault) p. 369
Common causes
- The DC link voltage is lower than the limits. p. 369
- The supply voltage is too low p. 369
- a defective component p. 369
- a defective input fuse p. 369
- the external charge switch is not closed p. 369
What to do
- If there is a temporary supply voltage break, reset the fault and restart the drive. p. 369
- Do a check of the supply voltage. If the supply voltage is sufficient, there is an internal fault. p. 369
- Examine the electrical network for fault. p. 369
- Ask instructions from the distributor near to you. p. 369
Before you service the product, read the safety instructions in the manual p. 88.