Ekn2 indicates an F4:2 tuning error where tuning required to leak inductance as specified with F4:2 cannot be performed, tuning required to boost torque as specified with #10 cannot be performed, or the capacity of the motor connected is 2 notches or more smaller than the inverter capacity. The manual's first action is: “Make sure that a motor is connected. Make sure that the motor is at standstill. Perform auto-tuning 1 again and if the error persists, perform tuning manually.”
- Model
- Toshiba VF-AS1
- Display shows
- F4:2 tuning error (Ekn2)
- Type
- Error code
- Source
- Manual p. 297
What Ekn2 means
F4:2 tuning error p. 297
Common causes
- Tuning required to leak inductance as specified with F4:2 cannot be performed. Tuning required to boost torque as specified with #10 cannot be performed. The capacity of the motor connected is 2 notches or more smaller than the inverter capacity. The motor connected is not a three-phase inductive motor. Tuning is performed while no motor is connected. The cables connecting the inverter to the motor are too long, they are more than 30m in length. Tuning is performed while the motor is running. p. 297
What to do
- Make sure that a motor is connected. Make sure that the motor is at standstill. Perform auto-tuning 1 again and if the error persists, perform tuning manually. p. 297
Before you service the product, read the safety instructions in the manual p. 17.
If Ekn2 is still not resolved
- Read the Instruction Manual p. 17 “Read the Instruction Manual.”
This page summarises what the manufacturer’s manual says about Ekn2; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Toshiba. Found a mistake? Report an error.