The TMS7 has detected a shorted SCR(s). The manual's first action is: “1. Determine the affected phase using the 3 phase indicators LEDs located on the left hand side of the TMS7 cover. Damaged SCRs are indicated by an extinguished phase indicator LED (all phase indicator LEDs should be illuminated when input voltage is present but the motor is not running). SCR damage can be verified using the Power Circuit Test described in the Test & Measurement chapter of this section. 2. Replace the damaged SCR. 3. Reset the trip condition by removing and reapplying control voltage to the TMS7.”
- Model
- TMS7 ME00070B
- Display shows
- Shorted SCR (0)
- Type
- Fault code
- Source
- Manual p. 29
What 0 means
Shorted SCR p. 29
Common causes
- The TMS7 has detected a shorted SCR(s). p. 29
Safety warnings — read before you start
- CAUTIONCAUTION. WARNING - ELECTRICAL SHOCK HAZARD The TMS7 contains dangerous voltages when connected to line voltage. Only a competent electrician should carry out the electrical installation. p. 3
What to do
- 1. Determine the affected phase using the 3 phase indicators LEDs located on the left hand side of the TMS7 cover. Damaged SCRs are indicated by an extinguished phase indicator LED (all phase indicator LEDs should be illuminated when input voltage is present but the motor is not running). SCR damage can be verified using the Power Circuit Test described in the Test & Measurement chapter of this section. 2. Replace the damaged SCR. 3. Reset the trip condition by removing and reapplying control voltage to the TMS7. p. 29
If 0 is still not resolved
- 1. Determine the affected phase using the 3 phase indicators LEDs located on the left hand side of the TMS7 cover. p. 29 “1. Determine the affected phase using the 3 phase indicators LEDs located on the left hand side of the TMS7 cover.”
This page summarises what the manufacturer’s manual says about 0; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with TMS7. Found a mistake? Report an error.