The Inverter I2T Overheat Protection fault occurs when there is inverter overload, the work/rest cycle time does not meet requirements, or the motor power exceeds the inverter's load capability. The manual's first action is: “Check the following: 1. The load’s work/rest cycle time must not exceed the specified allowable value. 2. Motor power (P0307) must match the inverter power (P0206).”
- Model
- Siemens MICROMASTER 440
- Display shows
- Inverter I2T Overheat Protection (F0005)
- Type
- Error code
- Source
- Manual p. 96
What F0005 means
Inverter I2T Overheat Protection p. 96
Common causes
- Inverter overload. p. 96
- Work/rest cycle time does not meet requirements. p. 96
- Motor power (P0307) exceeds the inverter’s load capability (P0206). p. 96
What to do
- Check the following: 1. The load’s work/rest cycle time must not exceed the specified allowable value. 2. Motor power (P0307) must match the inverter power (P0206). p. 96
Before you service the product, read the safety instructions in the manual p. 7.
If F0005 is still not resolved
This page summarises what the manufacturer’s manual says about F0005; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.