The Overcurrent fault occurs when there is a single-phase ground short circuit in the input line, the motor power does not match the inverter power, or there is a short circuit in the motor wiring. The manual's first action is: “The unit can continue operating. If there is a single-phase ground on the output, the MICROMASTER will trip and display fault code F0001.”
- Model
- Siemens MICROMASTER 440
- Display shows
- Overcurrent (F0001)
- Type
- Fault code
- Source
- Manual p. 33
What F0001 means
Overcurrent p. 33
Common causes
- When there is a single-phase ground short circuit in the input line p. 33
- The motor power (P0307) does not match the inverter power (P0206) p. 33
- Short circuit in the motor wiring p. 33
- Ground fault present p. 33
What to do
- The unit can continue operating. If there is a single-phase ground on the output, the MICROMASTER will trip and display fault code F0001. p. 33
- Check the following: 1. The motor power (P0307) must correspond to the inverter power (P0206). p. 33
- 2. Cable length must not exceed the allowed maximum. p. 33
- 3. No short circuits or ground faults in the motor cable or inside the motor. p. 33
- 4. The motor parameters entered into the inverter must match the actual motor being used. p. 33
- 5. The stator resistance value (P0350) entered into the inverter must be correct. p. 33
- 6. The motor cooling airflow path must be clear and the motor must not be overloaded. p. 33
- > Increase ramp time p. 33
- > Decrease the “boost” value p. 33
Before you service the product, read the safety instructions in the manual p. 7.
If F0001 is still not resolved
This page summarises what the manufacturer’s manual says about F0001; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.