Siemens MICROMASTER 440 Error F0003: Undervoltage

Siemens MICROMASTER 440 variable frequency drive · taken from the manufacturer’s manual, pages cited

Fault codeF0003

The Undervoltage fault occurs when there is a supply power fault or the inrush load exceeds the specified limit. The manual's first action is: “Check the following: 1. Supply voltage (P0210) must be within the range specified on the inverter nameplate. 2. Verify whether the supply experiences brief outages or transient voltage drops.”

Model
Siemens MICROMASTER 440
Display shows
Undervoltage (F0003)
Type
Fault code
Source
Manual p. 96

What F0003 means

Undervoltage p. 96

Common causes

  • Supply power fault. p. 96
  • Inrush load exceeds the specified limit. p. 96

What to do

  1. Check the following: 1. Supply voltage (P0210) must be within the range specified on the inverter nameplate. 2. Verify whether the supply experiences brief outages or transient voltage drops. p. 96

Before you service the product, read the safety instructions in the manual p. 7.

If F0003 is still not resolved

  • contact the dealer or service center p. 6
    “如果不遵守有关要求 不采取相应 措施 就会造成死亡或严重的人身伤害”
  • contact the dealer or service center p. 7
    “请仔细阅读这些“警告”,“注意”和“提示””

This page summarises what the manufacturer’s manual says about F0003; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.