Motor Parameter Auto‑Detection Fault means the motor parameter auto‑detection fault, load disappearance, current limit reached during auto‑detection, or detected stator resistance is less than 0.1 %. The manual's first action is: “0: Check that the motor is correctly connected to the inverter. 1‑40: Verify that motor parameters P304‑P311 are correct. Check whether the motor wiring is delta or star.”
- Model
- Siemens MICROMASTER 430
- Display shows
- Motor Parameter Auto‑Detection Fault (F0041)
- Type
- Alarm code
- Source
- Manual p. 86
What F0041 means
Motor Parameter Auto‑Detection Fault p. 86
Common causes
- Motor parameter auto‑detection fault. Alarm value = 0: Load disappearance. Alarm value = 1: Current limit reached during auto‑detection. Alarm value = 2: Detected stator resistance is less than 0.1 % or greater than 100 %. Alarm value = 3: Detected rotor resistance is less than 0.1 % or greater than 100 %. Alarm value = 4: Detected stator reactance is less than 50 % or greater than 500 %. Alarm value = 5: Detected supply reactance is less than 50 % or greater than 500 %. Alarm value = 6: Detected rotor time constant is less than 10 ms or greater than 5 s. Alarm value = 7: Detected total leakage reactance is less than 5 % or greater than 50 %. Alarm value = 8: Detected stator leakage reactance is less than 25 % or greater than 250 %. Alarm value = 9: Detected rotor leakage inductance is less than 25 % or greater than 250 %. Alarm value = 20: Detected IGBT on‑state voltage is less than 0.5 V or greater than 10 V. Alarm value = 30: Current controller reached voltage limit. Alarm value = 40: The data set from auto‑detection is internally inconsistent; at least one auto‑detected value is erroneous (based on reactance Zb percentage = Vrnot,norm / √3 / Irnot,norm). p. 86
What to do
- 0: Check that the motor is correctly connected to the inverter. 1‑40: Verify that motor parameters P304‑P311 are correct. Check whether the motor wiring is delta or star. p. 86
Before you service the product, read the safety instructions in the manual p. 7.
If F0041 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.
This page summarises what the manufacturer’s manual says about F0041; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.