Rectifier Overtemperature means insufficient ventilation airflow, cooling fan not operating, or ambient temperature too high. The manual's first action is: “Check the following: 1. The cooling fan must be running while the inverter is operating. 2. Pulse frequency must be set to the default value. 3. Ambient temperature may exceed the inverter’s allowable operating temperature.”
- Model
- Siemens MICROMASTER 430
- Display shows
- Rectifier Overtemperature (F0024)
- Type
- Fault code
- Source
- Manual p. 85
What F0024 means
Rectifier Overtemperature p. 85
Common causes
- Insufficient ventilation airflow, cooling fan not operating, ambient temperature too high. p. 85
What to do
- Check the following: 1. The cooling fan must be running while the inverter is operating. 2. Pulse frequency must be set to the default value. 3. Ambient temperature may exceed the inverter’s allowable operating temperature. p. 85
Before you service the product, read the safety instructions in the manual p. 7.
If F0024 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.
This page summarises what the manufacturer’s manual says about F0024; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.