Siemens MICROMASTER 430 Error F0005: Inverter I2T Overheat Protection

Siemens MICROMASTER 430 · taken from the manufacturer’s manual, pages cited

Error codeF0005

Inverter I2T Overheat Protection means the inverter overload or work/idle cycle time does not meet requirements. The manual's first action is: “Check the following: 1. The load's work/idle cycle time must not exceed the specified allowable value.”

Model
Siemens MICROMASTER 430
Display shows
Inverter I2T Overheat Protection (F0005)
Type
Error code
Source
Manual p. 84

What F0005 means

Inverter I2T Overheat Protection p. 84

Common causes

  • Inverter overload. p. 84
  • Work/idle cycle time does not meet requirements. p. 84

What to do

  1. Check the following: 1. The load's work/idle cycle time must not exceed the specified allowable value. p. 84
  2. 2. Motor power (P0307) must match the inverter power (P0206). p. 84

Before you service the product, read the safety instructions in the manual p. 7.

If F0005 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.

This page summarises what the manufacturer’s manual says about F0005; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.