Siemens G120C Error A30057: Power unit: Line asymmetry

Siemens G120C drive · taken from the manufacturer’s manual, pages cited

Fault codeA30057

The power unit has detected line asymmetry on the DC link voltage, possibly from phase failure or incorrect wiring in the motor or line connections. The manual's first action is: “- check the line phase connection. - check the motor feeder cable connections. If there is no phase failure of the line or motor, then line asymmetry is involved. - reduce the power in order to avoid fault F30011.”

Model
Siemens G120C
Display shows
Power unit: Line asymmetry (A30057)
Type
Fault code
Source
Manual p. 740

What A30057 means

Power unit: Line asymmetry p. 740

Common causes

  • Frequencies have been detected on the DC link voltage that would suggest line asymmetry or failure of a line phase. It is also possible that a motor phase has failed. p. 740

What to do

  1. - check the line phase connection. - check the motor feeder cable connections. If there is no phase failure of the line or motor, then line asymmetry is involved. - reduce the power in order to avoid fault F30011. p. 740

Before you service the product, read the safety instructions in the manual p. 4.

If A30057 is still not resolved

  • contact service / dealer p. 4
    “Warning concept This Manual contains information which you must observe to ensure your own personal safety as well as to avoid material damage.”
  • contact service / dealer p. 12
    “WARNING Danger to life if the safety instructions and residual risks are not observed”

This page summarises what the manufacturer’s manual says about A30057; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.