Error in parameterization/configuration/commissioning procedure due to system limit exceeded on the Siemens G120C. The manual's first action is: “OFF2 IMMEDIATELY At least one system overload has been identified. Fault value (r0949, interpret decimal): 1: Computing time load too high (r9976[1]). 5: Peak load too high (r9976[5]). Note: As long as this fault is present, it is not possible to save the parameters (p0971). See also: r9976 (System utilization)”
- Model
- Siemens G120C
- Display shows
- CU: System limit exceeded (F01054)
- Type
- Error code
- Source
- Manual p. 668
What F01054 means
CU: System limit exceeded p. 668
Common causes
- Error in the parameterization / configuration / commissioning procedure (18) p. 668
What to do
- OFF2 IMMEDIATELY At least one system overload has been identified. Fault value (r0949, interpret decimal): 1: Computing time load too high (r9976[1]). 5: Peak load too high (r9976[5]). Note: As long as this fault is present, it is not possible to save the parameters (p0971). See also: r9976 (System utilization) p. 668
Before you service the product, read the safety instructions in the manual p. 4.
If F01054 is still not resolved
This page summarises what the manufacturer’s manual says about F01054; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.