An error was detected evaluating parameter files PSxxxxxx ACX, PTxxxxxx ACX, CAXxxxxx ACX, or CCxxxxxx ACX saved in non-volatile memory on the Siemens G120C. The manual's first action is: “- check the parameters displayed in r9406 up to r9408, and correct these if required. - Restore the factory setting using (p0970 = 1) and re-load the project into the drive unit. Then save the parameterization in STARTER using the function "Copy RAM to ROM" or with p0971 = 1. This overwrites the incorrect parameter files in the non-volatile memory – and the alarm is withdrawn.”
- Model
- Siemens G120C
- Display shows
- Configuring data invalid (A0145)
- Type
- Error code
- Source
- Manual p. 668
What A0145 means
Configuring data invalid p. 668
Common causes
- An error was detected when evaluating the parameter files PSxxxxxx ACX, PTxxxxxx ACX, CAXxxxxx ACX, or CCxxxxxx ACX saved in the non-volatile memory. Because of this, under certain circumstances, several of the saved parameter values were not able to be accepted. p. 668
What to do
- - check the parameters displayed in r9406 up to r9408, and correct these if required. - Restore the factory setting using (p0970 = 1) and re-load the project into the drive unit. Then save the parameterization in STARTER using the function "Copy RAM to ROM" or with p0971 = 1. This overwrites the incorrect parameter files in the non-volatile memory – and the alarm is withdrawn. p. 668
Before you service the product, read the safety instructions in the manual p. 4.
If A0145 is still not resolved
This page summarises what the manufacturer’s manual says about A0145; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.