Siemens CU240S Error F00395: Acceptance Test / Confirmation pending

Siemens CU240S · taken from the manufacturer’s manual, pages cited

Fault codeF00395

Acceptance Test / Confirmation pending occurs after a Powermodul or Control Unit swap or startup clone, indicating parameters may need verification before operation. The manual's first action is: “The parameterset after a CU swap or a startup clone could have changed and might not match the application. This parameterset needs to be checked before the drive can start a motor.”

Model
Siemens CU240S
Display shows
Acceptance Test / Confirmation pending (F00395)
Type
Fault code
Source
Manual p. 390

What F00395 means

Acceptance Test / Confirmation pending p. 390

Common causes

  • This fault occurs after a Powermodul (PM) / Control Unit (CU) Swap or a Startup Clone. It can also be caused by a faulty read from the EEPROM, see F0051 for more details. p. 390
  • r0948 = 3 / 4: Swap of PM/CU p. 390
  • r0948 = 5: Startup Clone via MMC has been performed p. 390
  • r0948 = 10: Before the last power up an acceptance test was pending due to a swap or a startup clone. p. 390

What to do

  1. The parameterset after a CU swap or a startup clone could have changed and might not match the application. This parameterset needs to be checked before the drive can start a motor. p. 390

If F00395 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.

This page summarises what the manufacturer’s manual says about F00395; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.