Fault codeF00350
Configuration vector for the drive failed indicates that either hardware or software configuration does not match during startup, causing a trip. The manual's first action is: “Internal Failures can not be fixed.”
- Model
- Siemens CU240S
- Display shows
- Configuration vector for the drive failed (F00350)
- Type
- Fault code
- Source
- Manual p. 389
What F00350 means
Configuration vector for the drive failed p. 389
Common causes
- During startup the drive checks if the configuration vector (SZL vector) has been programmed correctly and if hw matches the programmed vector. If not the drive will trip. p. 389
- r0949 = 1: Internal Failure - No HW Configuration Vector available. p. 389
- r0949 = 2: Internal Failure - No SW Configuration Vector available. p. 389
- r0949 = 11: Internal Failure - CU Code not supported. p. 389
- r0949 = 12: Internal Failure - SW Vector not possible. p. 389
- r0949 = 13: Wrong power module fitted. p. 389
- r0949 > 1000: Internal failure - Wrong IO Board fitted. p. 389
- Note: Fault needs power cycle to be acknowledged. p. 389
What to do
If F00350 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.
This page summarises what the manufacturer’s manual says about F00350; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.