Siemens CU240S Error F00350: Configuration vector for the drive failed

Siemens CU240S · taken from the manufacturer’s manual, pages cited

Fault codeF00350

Configuration vector for the drive failed indicates that either hardware or software configuration does not match during startup, causing a trip. The manual's first action is: “Internal Failures can not be fixed.”

Model
Siemens CU240S
Display shows
Configuration vector for the drive failed (F00350)
Type
Fault code
Source
Manual p. 389

What F00350 means

Configuration vector for the drive failed p. 389

Common causes

  • During startup the drive checks if the configuration vector (SZL vector) has been programmed correctly and if hw matches the programmed vector. If not the drive will trip. p. 389
  • r0949 = 1: Internal Failure - No HW Configuration Vector available. p. 389
  • r0949 = 2: Internal Failure - No SW Configuration Vector available. p. 389
  • r0949 = 11: Internal Failure - CU Code not supported. p. 389
  • r0949 = 12: Internal Failure - SW Vector not possible. p. 389
  • r0949 = 13: Wrong power module fitted. p. 389
  • r0949 > 1000: Internal failure - Wrong IO Board fitted. p. 389
  • Note: Fault needs power cycle to be acknowledged. p. 389

What to do

  1. Internal Failures can not be fixed. p. 389
  2. Make sure the right power module is fitted p. 389

If F00350 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.

This page summarises what the manufacturer’s manual says about F00350; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.