The Siemens CU240S experienced a chip temperature rise exceeding critical levels, possibly from high startup load, large load steps, or too fast ramp-up rates. The manual's first action is: “Remedy: Check the following: • Load or load step too high? • Reduce ramp-up time (P1120). • Motor power (p0307) must match inverter power (r0206). • Use setting P0290 = 0 or 2 for preventing F00006.”
- Model
- Siemens CU240S
- Display shows
- Chip temperature rise exceeds critical levels. (F00006)
- Type
- Fault code
- Source
- Manual p. 380
What F00006 means
Chip temperature rise exceeds critical levels. p. 380
Common causes
- Reaction: OFF 2 Acknowledge: Quit fault eg. via DI2 Cause: • Load at start-up is too high • Load step is too high • Ramp-up rate is too fast p. 380
What to do
- Remedy: Check the following: • Load or load step too high? • Reduce ramp-up time (P1120). • Motor power (p0307) must match inverter power (r0206). • Use setting P0290 = 0 or 2 for preventing F00006. p. 380
If F00006 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.
This page summarises what the manufacturer’s manual says about F00006; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.