Fault codeF00001
The Siemens CU240S detected an overcurrent condition due to motor power mismatch or a short circuit in the motor leads. The manual's first action is: “Quit fault eg. via D12”
- Model
- Siemens CU240S
- Display shows
- Overcurrent (F00001)
- Type
- Fault code
- Source
- Manual p. 379
What F00001 means
Overcurrent p. 379
Common causes
- OFF 2 p. 379
- Motor power (p0307) does not correspond to the inverter power (r0206) p. 379
- Motor lead short circuit p. 379
- Earth faults p. 379
- Check the following: p. 379
- Cable length limits must not be exceeded. p. 379
- Motor cable and motor must have no short-circuits or earth faults p. 379
- Motor parameters must match the motor in use p. 379
- Value of stator resistance (p0350) must be correct p. 379
- Motor must not be obstructed or overloaded p. 379
- Increase Ramp-up time (p1120) p. 379
- Reduce Starting boost level (p1312) p. 379
- r0948 = 0: HW reported p. 379
- r0948 = 1: SW reported p. 379
What to do
If F00001 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.
This page summarises what the manufacturer’s manual says about F00001; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.