Siemens CU240S Error F00002: Overvoltage

Siemens CU240S · taken from the manufacturer’s manual, pages cited

Fault codeF00002

The Siemens CU240S detected an overvoltage condition caused by high mains voltage or regenerative mode operation. The manual's first action is: “Quit fault eg. via D12”

Model
Siemens CU240S
Display shows
Overvoltage (F00002)
Type
Fault code
Source
Manual p. 379

What F00002 means

Overvoltage p. 379

Common causes

  • OFF 2 p. 379
  • Main supply voltage too high p. 379
  • Motor is in regenerative mode p. 379
  • Check the following: p. 379
  • Vdc controller must be enabled (p1240) and parameterized properly. p. 379
  • Ramp-down time (p1121) must match inertia of load. p. 379
  • Required braking power must lie within specified limits. p. 379
  • Regenerative mode can be caused by fast ramp downs or if the motor is driven by an active load. p. 379
  • r0948 = 1 or 2: SW reported p. 379
  • Higher inertia requires longer ramp times; otherwise, apply braking resistor. p. 379

What to do

  1. Quit fault eg. via D12 p. 379
  2. Supply voltage (p0210) must lie within limits indicated on rating plate . p. 379
  3. r0948 = 0: HW reported p. 379

If F00002 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.

This page summarises what the manufacturer’s manual says about F00002; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.