Fault codeF00002
The Siemens CU240S detected an overvoltage condition caused by high mains voltage or regenerative mode operation. The manual's first action is: “Quit fault eg. via D12”
- Model
- Siemens CU240S
- Display shows
- Overvoltage (F00002)
- Type
- Fault code
- Source
- Manual p. 379
What F00002 means
Overvoltage p. 379
Common causes
- OFF 2 p. 379
- Main supply voltage too high p. 379
- Motor is in regenerative mode p. 379
- Check the following: p. 379
- Vdc controller must be enabled (p1240) and parameterized properly. p. 379
- Ramp-down time (p1121) must match inertia of load. p. 379
- Required braking power must lie within specified limits. p. 379
- Regenerative mode can be caused by fast ramp downs or if the motor is driven by an active load. p. 379
- r0948 = 1 or 2: SW reported p. 379
- Higher inertia requires longer ramp times; otherwise, apply braking resistor. p. 379
What to do
- Quit fault eg. via D12 p. 379
- Supply voltage (p0210) must lie within limits indicated on rating plate . p. 379
- r0948 = 0: HW reported p. 379
If F00002 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.
This page summarises what the manufacturer’s manual says about F00002; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.