Fault codeF30600
Processor 2’s Safety Integrated function initiated a STOP A due to an error during safety shutdown path checking or response to fault F30611. The manual lists no action for this code.
- Model
- Siemens CU240B/E-2
- Display shows
- SI P2: STOP A initiated (F30600)
- Type
- Fault code
- Source
- Manual p. 720
What F30600 means
SI P2: STOP A initiated p. 720
Common causes
- The drive-integrated "Safety Integrated" function on processor 2 has detected an error and initiated a STOP A. p. 720
- - forced checking procedure of the safety shutdown path via processor 2 unsuccessful. p. 720
- - subsequent response to fault F30611 (defect in a monitoring channel). p. 720
- Fault value (r0949, decimal interpretation): p. 720
- 0: Stop request from processor 1. p. 720
- 1005: Pulses suppressed although STO not selected and there is no internal STOP A present. p. 720
- 1010: Pulses enabled although STO is selected or an internal STOP A is present. p. 720
- 9999: Subsequent response to fault F30611. p. 720
If F30600 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.
This page summarises what the manufacturer’s manual says about F30600; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.