Siemens CU240B/E-2 Error F30600: SI P2: STOP A initiated

Control unit · taken from the manufacturer’s manual, pages cited

Fault codeF30600

Processor 2’s Safety Integrated function initiated a STOP A due to an error during safety shutdown path checking or response to fault F30611. The manual lists no action for this code.

Model
Siemens CU240B/E-2
Display shows
SI P2: STOP A initiated (F30600)
Type
Fault code
Source
Manual p. 720

What F30600 means

SI P2: STOP A initiated p. 720

Common causes

  • The drive-integrated "Safety Integrated" function on processor 2 has detected an error and initiated a STOP A. p. 720
  • - forced checking procedure of the safety shutdown path via processor 2 unsuccessful. p. 720
  • - subsequent response to fault F30611 (defect in a monitoring channel). p. 720
  • Fault value (r0949, decimal interpretation): p. 720
  • 0: Stop request from processor 1. p. 720
  • 1005: Pulses suppressed although STO not selected and there is no internal STOP A present. p. 720
  • 1010: Pulses enabled although STO is selected or an internal STOP A is present. p. 720
  • 9999: Subsequent response to fault F30611. p. 720

If F30600 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.

This page summarises what the manufacturer’s manual says about F30600; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.