Fault codeF30611
Processor 2 detected a monitoring channel defect, causing it to trigger STOP A and resulting in fault F30600. The manual's first action is: “As a consequence of this fault, fault F30600 (SI P2: STOP A initiated) is output.”
- Model
- Siemens CU240B/E-2
- Display shows
- SI P2: Defect in a monitoring channel (F30611)
- Type
- Fault code
- Source
- Manual p. 721
What F30611 means
SI P2: Defect in a monitoring channel p. 721
Common causes
- The drive-integrated "Safety Integrated" function on processor 2 has detected a fault in the crosswise data comparison between the two monitoring channels and has initiated a STOP F. p. 721
- Fault value (r0949, decimal interpretation): 0: Stop request from processor 1. p. 721
- 2: SI enable safety functions (p9601, p9801). Crosswise data comparison is only carried out for the supported bits. p. 721
- 8: SI PROFIsafe address (p9610, p9810). p. 721
- 1000: Watchdog timer has expired. Within a time of approx. 5 x p9850, too many switching operations have occurred at F-DI, or STO (also as subsequent response) was initiated too frequently via PROFIsafe. p. 721
- 2000: Status of the STO selection for both monitoring channels are different. p. 721
- 6000 ... 6999: Error in the PROFIsafe control. p. 721
What to do
- As a consequence of this fault, fault F30600 (SI P2: STOP A initiated) is output. p. 721
- 1 ... 999: Number in the cross-checked data that resulted in this fault. This number is also displayed in r9795. p. 721
- 3: SI F-DI changeover tolerance time (p9650, p9850). p. 721
- 9: SI debounce time for STO (p9651, p9851). p. 721
- 1001, 1002: Initialization error, change timer / check timer. p. 721
- 2001: Feedback of the safe pulse suppression on the two monitoring channels are different. p. 721
- For these fault values, the failsafe control signals (failsafe values) are transferred to the safety functions. The significance of the individual message values is described in safety message C01711. p. 721
- Remedy: Re fault values 1 ... 999 described as "Cause": - check the cross-checked data that resulted in a STOP F. - carry out a POWER ON (power off/on). p. 721
- For fault value = 1000: - check the wiring of the F-DI (contact problems). - PROFIsafe: Remove contact problems/fauls at the PROFIbus master/PROFINET controller. Re fault value = 1001, 1002: - carry out a POWER ON (power off/on). p. 721
- Re fault value = 2000, 2001, 2002, 2004, 2005: - check the tolerance time F-DI changeover and if required, increase the value (p9650/p9850). - check the wiring of the F-DI (contact problems). p. 721
- - check the causes of the STO selection in r9772. When the SI Motion functions are active (p9501 = 1), STO can also be selected using these functions. p. 721
- Re fault value = 6000 ... 6999: - Refer to the description of the message values in safety message C01711. - Re fault values that are described as "Cause": - carry out a POWER ON (power off/on). p. 721
- - contact the Hotline - replace Control Unit. p. 721
- Note: F-DI: Failsafe Digital Input STO: Safe Torque Off p. 721
If F30611 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.
This page summarises what the manufacturer’s manual says about F30611; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.