Siemens 352P Error ERR288: The LonWorks circuit board currently installed is not compatible with the LonWorks configuration contained on the Board.

Siemens 352P controller · taken from the manufacturer’s manual, pages cited

Error codeERR288

The LonWorks circuit board installed is not compatible with the configuration on the Board. The manual's first action is: “1) Power down and install the LonWorks board from the same controller that the Board came from.”

Model
Siemens 352P
Display shows
ERR288
Type
Error code
Source
Manual p. 263

What ERR288 means

The LonWorks circuit board currently installed is not compatible with the LonWorks configuration contained on the Board. p. 263

What to do

  1. 1) Power down and install the LonWorks board from the same controller that the Board came from. p. 263
  2. 2) Press ENTER to ACK error. Controller will go on-line. Any existing LonWorks network data will be used if it is valid, otherwise, it will be set to default values. In either case, the LonWorks network manager will be required to re-establish the network bindings. p. 263

Before you service the product, read the safety instructions in the manual p. 11.

If ERR288 is still not resolved

  • contact service / dealer p. 12
    “Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes,”
  • contact service / dealer p. 12
    “the matter should be referred to one of the support groups listed in the Product Support section of this manual.”

This page summarises what the manufacturer’s manual says about ERR288; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.