SEW MOVITRAC-07 Error 08: Speed monitoring

Frequency inverter · taken from the manufacturer’s manual, pages cited

Fault code08

Code 08 indicates speed monitoring when the current controller is operating at the setting limit due to mechanical overload, phase failure in supply system, or phase failure in motor. The manual's first action is: “Reduce load”

Model
SEW MOVITRAC-07
Display shows
Speed monitoring (08)
Type
Fault code
Source
Manual p. 45

What 08 means

Speed monitoring p. 45

Common causes

  • Current controller is operating at the setting limit due to: mechanical overload p. 45
  • phase failure in supply system p. 45
  • phase failure in motor p. 45
  • Maximum speed for VFC operating mode exceeded p. 45

What to do

  1. Reduce load p. 45
  2. Increase delay time setting P501 p. 45
  3. Check current limitation p. 45
  4. Extend deceleration ramps p. 45
  5. Check supply system phases p. 45
  6. Check motor feeder and motor p. 45
  7. Reduce maximum speed p. 45

If 08 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact SEW service.