Fault code04
Code 04 indicates a brake chopper issue caused by excessive regenerative power, interrupted braking resistor circuit, or short circuit in braking resistor circuit. The manual's first action is: “Extend deceleration ramps”
- Model
- SEW MOVITRAC-07
- Display shows
- Brake chopper (04)
- Type
- Fault code
- Source
- Manual p. 45
What 04 means
Brake chopper p. 45
Common causes
- Regenerative power excessive p. 45
- Braking resistor circuit interrupted p. 45
- Short circuit in braking resistor circuit p. 45
- Excessively high braking resistance p. 45
- Brake chopper defective p. 45
- Ground fault p. 45
What to do
- Extend deceleration ramps p. 45
- Check connecting harness for braking resistor p. 45
- Rectify the short circuit p. 45
- Check technical data of braking resistor p. 45
- Replace the MOVITRAC® 07 p. 45
- Rectify the ground fault p. 45
If 04 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact SEW service.
This page summarises what the manufacturer’s manual says about 04; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with SEW. Found a mistake? Report an error.