SEW MOVITRAC-07 Error 01: Over-current

Frequency inverter · taken from the manufacturer’s manual, pages cited

Fault code01

Code 01 indicates an over-current condition caused by a short circuit on output, output switching, or motor too large. The manual's first action is: “Rectify the short circuit”

Model
SEW MOVITRAC-07
Display shows
Over-current (01)
Type
Fault code
Source
Manual p. 45

What 01 means

Over-current p. 45

Common causes

  • Short circuit on output p. 45
  • Output switching p. 45
  • Motor too large p. 45
  • Defective output stage p. 45
  • Ramp limit (P138) switched off p. 45

What to do

  1. Rectify the short circuit p. 45
  2. Only switch when output stage inhibited p. 45
  3. Connect a smaller motor p. 45
  4. Call SEW Service for advice if the fault still cannot be reset p. 45
  5. Ramp limit (P138 = YES) p. 45

If 01 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact SEW service.