Schneider Electric ATV 31H Error USF: Undervoltage

Variable speed drive · taken from the manufacturer’s manual, pages cited

Fault codeUSF

Undervoltage is triggered by low line supply, transient voltage dip, or damaged load resistor. The manual's first action is: “Check the voltage and the voltage parameter. USF trip threshold ATV31••••M2: 160V ATV31••••M3X: 160V ATV31••••N4: 300V ATV31••••S6X: 430V”

Model
Schneider Electric ATV 31H
Display shows
Undervoltage (USF)
Type
Fault code
Source
Manual p. 93

What USF means

Undervoltage p. 93

Common causes

  • Line supply too low p. 93
  • Transient voltage dip p. 93
  • Damaged load resistor p. 93

What to do

  1. Check the voltage and the voltage parameter. USF trip threshold ATV31••••M2: 160V ATV31••••M3X: 160V ATV31••••N4: 300V ATV31••••S6X: 430V p. 93
  2. Replace the drive. p. 93

Before you service the product, read the safety instructions in the manual p. 56.

If USF is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.

This page summarises what the manufacturer’s manual says about USF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.