Schneider Electric ATV 31H Error DPF: Motor phase loss

Variable speed drive · taken from the manufacturer’s manual, pages cited

Fault codeDPF

Motor phase loss occurs due to loss of one phase at drive output, downstream contactor open, or motor not connected or power too low. The manual's first action is: “Check the connections from the drive to the motor.”

Model
Schneider Electric ATV 31H
Display shows
Motor phase loss (DPF)
Type
Fault code
Source
Manual p. 93

What DPF means

Motor phase loss p. 93

Common causes

  • Loss of one phase at drive output p. 93
  • Downstream contactor open p. 93
  • Motor not connected or motor power too low p. 93
  • Instantaneous instability in the motor current p. 93

What to do

  1. Check the connections from the drive to the motor. p. 93
  2. If a downstream contactor is being used, set OPL to OAC (FLT- menu page 67). p. 93
  3. Test on a low power motor or without a motor: In factory settings mode, motor phase loss detection is active (OPL = YES). To check the drive in a test or maintenance environment without having to switch to a motor with the same rating as the drive (particularly useful in the case of high power drives), deactivate motor phase loss detection (OPL = no). p. 93
  4. Check and optimize the UFr (page 20), UnS and nCr (page 23) parameters and perform auto-tuning with tUn (page 24). p. 93

Before you service the product, read the safety instructions in the manual p. 56.

If DPF is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.

This page summarises what the manufacturer’s manual says about DPF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.