Motor phase loss occurs due to loss of one phase at drive output, downstream contactor open, or motor not connected or power too low. The manual's first action is: “Check the connections from the drive to the motor.”
- Model
- Schneider Electric ATV 31H
- Display shows
- Motor phase loss (DPF)
- Type
- Fault code
- Source
- Manual p. 93
What DPF means
Motor phase loss p. 93
Common causes
- Loss of one phase at drive output p. 93
- Downstream contactor open p. 93
- Motor not connected or motor power too low p. 93
- Instantaneous instability in the motor current p. 93
What to do
- Check the connections from the drive to the motor. p. 93
- If a downstream contactor is being used, set OPL to OAC (FLT- menu page 67). p. 93
- Test on a low power motor or without a motor: In factory settings mode, motor phase loss detection is active (OPL = YES). To check the drive in a test or maintenance environment without having to switch to a motor with the same rating as the drive (particularly useful in the case of high power drives), deactivate motor phase loss detection (OPL = no). p. 93
- Check and optimize the UFr (page 20), UnS and nCr (page 23) parameters and perform auto-tuning with tUn (page 24). p. 93
Before you service the product, read the safety instructions in the manual p. 56.
If DPF is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.
This page summarises what the manufacturer’s manual says about DPF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.