Schneider Electric Altivar 61 Error OPF2: [3 motor phase loss]

Altivar 61 drive · taken from the manufacturer’s manual, pages cited

Fault codeOPF2

OPF2 indicates motor not connected or motor power too low, output contactor open, or instantaneous instability in the motor current. The manual's first action is: “Check the connections from the drive to the motor.”

Model
Schneider Electric Altivar 61
Display shows
[3 motor phase loss] (OPF2)
Type
Fault code
Source
Manual p. 56

What OPF2 means

[3 motor phase loss] p. 56

Common causes

  • Motor not connected or motor power too low p. 56
  • Output contactor open p. 56
  • Instantaneous instability in the motor current p. 56

What to do

  1. Check the connections from the drive to the motor. p. 56
  2. If an output contactor is being used, consult the CD-ROM supplied with the drive. p. 56
  3. Test on a low power motor or without a motor: In factory settings mode, motor output phase loss detection is active [Output Phase Loss] (OPL) = [Yes] (YES). To check the drive in a test or maintenance environment without having to switch to a motor with the same rating as the drive (particularly useful in the case of high-power drives), deactivate output phase loss detection [Output phase loss] (OPL) = [No] (nC). p. 56
  4. Check and optimize the [Rated motor volt.] (UnS) and [Rated mot. current.] (nCr) parameters and perform an [Auto tuning] (tUn) operation. p. 56

Before you service the product, read the safety instructions in the manual p. 33.

If OPF2 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.

This page summarises what the manufacturer’s manual says about OPF2; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.