Schneider Electric Altivar 61 Error ObF: [Overbraking]

Altivar 61 drive · taken from the manufacturer’s manual, pages cited

Fault codeObF

ObF indicates braking too sudden or driving load, or drive temperature too high. The manual's first action is: “Increase the deceleration time.\nInstall a braking resistor if necessary.\nActivate the [Dec ramp adapt.] (brA) function (consult the CD-ROM supplied with the drive), if it is compatible with the application.”

Model
Schneider Electric Altivar 61
Display shows
[Overbraking] (ObF)
Type
Fault code
Source
Manual p. 55

What ObF means

[Overbraking] p. 55

Common causes

  • Braking too sudden or driving load p. 55
  • Drive temperature too high p. 55

What to do

  1. Increase the deceleration time.\nInstall a braking resistor if necessary.\nActivate the [Dec ramp adapt.] (brA) function (consult the CD-ROM supplied with the drive), if it is compatible with the application. p. 55
  2. Check the motor load, the drive ventilation and the ambient temperature. Wait for the drive to cool down before restarting. p. 55

Before you service the product, read the safety instructions in the manual p. 33.

If ObF is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.

This page summarises what the manufacturer’s manual says about ObF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.