Schneider Electric Altivar 21 Error OCA: Arm overcurrent during startup

Altivar 21 variable speed drive · taken from the manufacturer’s manual, pages cited

Fault codeOCA

Arm overcurrent during startup means a ground fault occurred. The manual's first action is: “Using a 1000 V megger, check the motor and motor cables for ground faults.”

Model
Schneider Electric Altivar 21
Display shows
Arm overcurrent during startup (OCA)
Type
Fault code
Source
Manual p. 119

What OCA means

Arm overcurrent during startup p. 119

Common causes

What to do

  1. Using a 1000 V megger, check the motor and motor cables for ground faults. p. 119

Before you service the product, read the safety instructions in the manual p. 5.

If OCA is still not resolved

  • contact Schneider Electric service p. 5
    “Schneider Electric accepts no responsibility for the consequences of using this device”
  • contact a qualified technician p. 6
    “Installation, adjustment, repair, and maintenance must be performed by qualified personnel”

This page summarises what the manufacturer’s manual says about OCA; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.